1. Power Knowledge Center
  2. Event Code Help (F0 - F65)

F11 Code Help – Timer (Programmable)

F11 (All Drives): Timer

Code Meaning: The motor has run longer than that allotted by the timer setting at L24.

Further Information/Troubleshooting Tips:

  1. Cause: Unattended motor driven device stalled or jammed. Solution: Investigate why motor stalled and correct problem. Perhaps the load was heavy enough to cause the motor not to turn in low speed due to excessive slip. Increasing the voltage boost (A8) or low speed setting (A12) might help.
  2. Cause: Programmer accidentally enabled the timer. Solution: Disable the timer by setting L24 to zero.
  3. Cause: Timer set for too short of a period. Solution: Increase time set in L24.

Call PE® for further assistance if needed.